IEDs energy measurement stops at 65.536 MWh

IEDs energy measurement stops at 65.536 MWh

This is known issue with firmware version of v1.0.8-115-g5e39c58.




Situation can be remedied with firmware update. Please contact our support and ask for firmware update package for this fix.

When contacting support please indicate relay serial number so that we can offer correct firmware version.

    • Related Articles

    • Does Motor Protection IED use motor nominal or CT nominal for protection? Are residual currents also scaled?

      By default all AQ-200 series Motor Protection IEDs use scale current pick-up settings to current transformer nominal values. If the settings need to be scaled to the motors nominal current instead navigate to Protection > Motor Module > INFO and ...
    • Enabling THD measurement

      In AQ-200 product series current THD measurement is unique from other measurements in a way that it needs to be manually enabled if such measurement is needed. This can be done by enabling THD mode in Monitoring > Monitors enabled.
    • Technical difference between AQ-200 IED residual current channels Io1 and Io2

      Every AQ-200 series IED equipped with current transformer module has two residual current channels Io1 and Io2. All protection and control functions that use residual current require the user to choose which of these two residual current channels is ...
    • Modbus communication in AQ-200 series IEDs

      AQ-200 series devices can communicate using both Modbus RTU serial protocol and Modbus TCP protocol. Same data can be accessed using both these protocols. To use Modbus TCP it can be activated with parameter Modbus TCP enable in menu Communication à ...
    • 3-phase, 3-wire ARON input connection example

      This chapter presents a connection example of an application with protection current transformers for just two phases. Connection is suitable for both motor –and feeder protection applications. ARON input connection can measure load symmetrically ...