Rated voltage and nominal voltages of digital inputs in CPU card and option cards

Rated voltage and nominal voltages of digital inputs in CPU card and option cards

Nominal and rated voltages of digital inputs on main CPU board

All AQ-200 series units always come with two or three digital inputs in the main CPU board. The rated voltage (maximum operation voltage) of these inputs are always 265 V (AC/DC). The nominal voltage of these digital inputs can be 24, 110 and 220 V (AC/DC). Nominal voltage defines the voltage level at which digital input activates and deactivates. Nominal voltage of these digital inputs is done when ordering the units.

Nominal voltage V (AC/DC)
Activation threshold V (AC/DC)
Release threshold V (AC/DC)
Rated voltage V (AC/DC)
24
19
14
265
110
90
65
265
220
170
132
265

Nominal and rated voltages of digital inputs on option cards

All AQ-200 series can be ordered with digital input option cards to extend the functionality of the device (with the exception of AQ-F201). These digital inputs also have rated voltage of 265 V (AC/DC) but there isn't any nominal voltage. Instead the activation voltage and release voltage thresholds are defined when configuring the device.

Activation threshold V (AC/DC)
Release threshold V (AC/DC)
Rated voltage V (AC/DC)
16...200
10...200
265





    • Related Articles

    • Adding or replacing an option card

      If a new option card has been added a script must be run to the relay which updates the hardware configuration of the relay and updates the menu structure. To start the process contact Arcteq Support and list the following details: - Relays serial ...
    • Set up AVR (automatic voltage regulator) tap changer position with mA inputs

      AQ-200 series IEDs equipped with automatic voltage regulator are able to detect the tap position with mA inputs, BCD coded digital inputs and digital input voltage measurement. This guide will walk you through how to set up AVR tap changer position ...
    • Digital input activation troubleshooting

      In case you are having issues with digital inputs not activating when they clearly should be, having a quick look into the Binary Inputs-menu either with AQtivate (shown below) or the relays HMI display. If none of the digital inputs activate the ...
    • Set all digital input thresholds with just a few clicks

      In case you have a lot of digital inputs to configure and all of them have the same voltage connected there is a tool in AQtivate setting tool which will help you set up the voltage threshold of all digital inputs at once. Simply navigate to Tools > ...
    • Tap changer position indication with digital inputs in "binary coded inputs" and "BCD-inputs" mode

      Sometimes tap position is done by using multiple digital inputs. There are two methods for doing this: binary coded decimal (BCD) inputs and binary coded inputs. Both support up to five digital inputs but they use a different number format. Whereas ...