Retrieving DR files from AQ200 series with other client than Aqtivate
FTP
DR files can be downloaded using standard
ftp client.
Note the following:
Username: ftp
Password: ftp
Root dir: the DR files are stored in
/ftp/records directory.
IEC61850 transfer file
DR files can be downloaded
using IEC61850 client.
Note that the DR files are stored in
ftp/records directory.
If there are problems retrieving DR files
using IEC61850 client, check the following:
Is File service enabled in the cid-file? <FileHandling/>
must be present under Services. If not it is possible that the device firmware
needs to be upgraded.
‘ftp’ or ‘ftp/records’ directory is not
visible in root dir? Ask Arcteq support for help. Issue can be solved using
script file.
Related Articles
Disturbance recorder setting recommendations
Disturbance recorder can be extremely helpful in analyzing the reason for protection function trips. Disturbance recordings use standard COMTRADE file format. This means the recording files can be opened by any software that supports COMTRADE format. ...
Troubleshooting not being able to load disturbance recordings from the relay
If the disturbance recorder function has recordings in memory but clicking Disturbance recorder > Get DR files results in No more DR files to get message check the user defined Device name and Device location in General-menu. If either of those have ...
Downloading AQtivate 200 setting tool
To download AQtivate 200 setting tool visit our website https://arcteq.fi/ and log in to our website. Once logged in you should find download link for AQtivate 200 installer at https://arcteq.fi/downloads/ To get full use of the features included in ...
How to fix "Unable to get the list from the FTP server" error message.
When updating the firmware of AQ-200 series device some users get the following error message. To fix this go to Tools > Settings and change FTP mode from "Active" to "Passive".
Load report file from the AQ-300 IED for faster technical support
In case of having technical issues with AQ-300 series IED it is advised to load a “report file” from the relay to help Arcteq Relays to determine the cause for the issue faster. The report file may contain information valuable for the manufacturer. ...