Setting thermal capacity manually when testing line/machine/transformer thermal overload protection

Setting thermal capacity manually when testing line/machine/transformer thermal overload protection

When testing thermal overload protection functions resetting the thermal capacity it often needed so that the test can be repeated multiple times without having to wait for the thermal cap to got down. This can be done with parameter Cold reset theta default. This parameter can be found at INFO page of line/machine/transformer thermal overload function. The value written to this parameter will be the new thermal capacity value used by the function.

NOTE: This value also defines the default theta value when the function is reset. Keep this in mind after using the parameter for manual adjustments.
    • Related Articles

    • Switching between setting groups manually

      Sometimes testing the protection functions in each setting group can get very time consuming if switching between the setting groups requires a very difficult to achieve condition. In these cases it is possible to temporarily change the setting group ...
    • Change setting groups manually to ease commissioning tests

      Sometimes testing the protection functions in each setting group can be laborious if changing the settings group activation requires a very specific condition. To work around this it is possible to temporarily change the setting group manually by ...
    • AQ-200 Current transformer selection

      Introduction Current transformer selection is important part of complete protection system design. Current transformer must be able to measure currents according to the application needs in all situations. Specifying current transformers is sometimes ...
    • Test events generation with stage forcing

      When testing event signaling to communication it might be time consuming to connect a relay testidevice and induce voltages and current especially if the protection functions have already been commissioned. To test if the RTU receives the signals ...
    • 3-phase, 3-wire ARON input connection example

      This chapter presents a connection example of an application with protection current transformers for just two phases. Connection is suitable for both motor –and feeder protection applications. ARON input connection can measure load symmetrically ...