Timesynchronization with DNP3 communication protocol
Enabling serial based DNP3
Serial DNP3 can be enabled with
Protocol parameter
at
Communication > Connections menu at
Serial section.
Set the
Slave address and other settings at
Communication > Protocols
> DNP3.
Serial based time synchronization
In general when serial time synchronization is used with DNP3 it is expected that the time sent to relay is UTC time. In this case the time zone should be set at Commands > Set time zone. This setting will correct the time displayed on AQ-200 unit clock and timestamps in event history. The events reported to SCADA will use UTC time.
If local time is sent to relay instead of UTC time, no time zone setting should be set. If time zone has been set to the relay this can be reversed by setting Etc/UTC as the time zone.
Enabling TCP based DNP3
TCP based DNP3 can be enabled at Communication > Protocols > DNP3 with
DNP TCP enable parameter
. Set the IP address used by DNP3 at Communication > Connections.Time synchronization
Set Time sync. source parameter to NTP at General menu. Set the NTP server IP address at Communication > Protocols > NTP. AQ-21x frame units need also client IP address set that is unique from the IP address set at Communication > Connections.
Time zone
In general when NTP time synchronization is used with DNP3 TCP it is expected that the time sent to relay is UTC time. In this case the time zone should be set at Commands > Set time zone. This setting will correct the time displayed on AQ-200 unit clock and timestamps in event history. The events reported to SCADA will use UTC time.
If local time is sent to relay instead of UTC time, no time zone setting should be set. If time zone has been set to the relay this can be reversed by setting Etc/UTC as the time zone.
Related Articles
Timesynchronization with IEC101 communication protocol
Enabling IEC101 IEC101 can be enabled with Protocol parameter at Communication > Connections menu at Serial section. Set the IEC101 addresses at Communication > Protocols > IEC101/104. Time synchronization Set Time sync. ...
Timesynchronization with IEC103 communication protocol
Enabling IEC103 IEC103 can be enabled with Protocol parameter at Communication > Connections menu at Serial section. Set the Slave address at Communication > Protocols > IEC103. Time synchronization Set Time sync. ...
Timesynchronization with SPA communication protocol
Enabling SPA SPA can be enabled with Protocol parameter at Communication > Connections menu at Serial section. Set the SPA address at Communication > Protocols > SPA. Time synchronization Set Time sync. source parameter to Serial at General menu. ...
Timesynchronization with IEC104 communication protocol
Enabling IEC104 IEC104 can be enabled at Communication > Protocols > IEC101/104 menu. Time synchronization Set Time sync. source parameter to Serial at General menu. Time zone When serial time synchronization is used with IEC101 it is expected that ...
Timesynchronization with IEC61850 communication protocol
Enabling IEC61850 IEC61850 can be enabled at Communication > Protocols > IEC61850. Set the IP address used by IEC61850 at Communication > Connections. Time synchronization Set Time sync. source parameter to NTP at General menu. Set the NTP server IP ...