Timesynchronization with IEC101 communication protocol
Enabling IEC101
IEC101 can be enabled with Protocol parameter at Communication > Connections menu at Serial section. Set the IEC101 addresses at Communication > Protocols > IEC101/104.
Time synchronization
Set Time sync. source parameter to Serial at General menu.
Time zone
When serial time synchronization is used with IEC101 it is expected that the time sent to relay is local time. No time zone corrections are done in the AQ-200 unit.
Related Articles
Timesynchronization with IEC103 communication protocol
Enabling IEC103 IEC103 can be enabled with Protocol parameter at Communication > Connections menu at Serial section. Set the Slave address at Communication > Protocols > IEC103. Time synchronization Set Time sync. ...
Timesynchronization with SPA communication protocol
Enabling SPA SPA can be enabled with Protocol parameter at Communication > Connections menu at Serial section. Set the SPA address at Communication > Protocols > SPA. Time synchronization Set Time sync. source parameter to Serial at General menu. ...
Timesynchronization with DNP3 communication protocol
Enabling serial based DNP3 Serial DNP3 can be enabled with Protocol parameter at Communication > Connections menu at Serial section. Set the Slave address and other settings at Communication > Protocols > DNP3. Serial based time synchronization In ...
Timesynchronization with IEC104 communication protocol
Enabling IEC104 IEC104 can be enabled at Communication > Protocols > IEC101/104 menu. Time synchronization Set Time sync. source parameter to Serial at General menu. Time zone When serial time synchronization is used with IEC101 it is expected that ...
Timesynchronization with IEC61850 communication protocol
Enabling IEC61850 IEC61850 can be enabled at Communication > Protocols > IEC61850. Set the IP address used by IEC61850 at Communication > Connections. Time synchronization Set Time sync. source parameter to NTP at General menu. Set the NTP server IP ...