Timesynchronization with SPA communication protocol
Enabling SPA
SPA can be enabled with Protocol parameter at Communication > Connections menu at Serial section. Set the SPA address at Communication > Protocols > SPA.
Time synchronization
Set Time sync. source parameter to Serial at General menu.
Time zone
In general when serial time synchronization is used with SPA it is expected that the time sent to relay is local time.
If UTC time is sent to relay instead of local time, set UTC time sync to Enabled at Communication > Protocols > SPA. In this case the time zone should be set at Commands > Set time zone. This setting will correct the time displayed on AQ-200 unit clock and timestamps in event history. The events reported to SCADA will use UTC time.
Related Articles
Timesynchronization with DNP3 communication protocol
Enabling serial based DNP3 Serial DNP3 can be enabled with Protocol parameter at Communication > Connections menu at Serial section. Set the Slave address and other settings at Communication > Protocols > DNP3. Serial based time synchronization In ...
Timesynchronization with IEC101 communication protocol
Enabling IEC101 IEC101 can be enabled with Protocol parameter at Communication > Connections menu at Serial section. Set the IEC101 addresses at Communication > Protocols > IEC101/104. Time synchronization Set Time sync. ...
Timesynchronization with ModbusRTU and Modbus TCP communication protocols
When Modbus communication protocol is used, time synchronization setup depends on which type of Modbus is used: ModbutRTU (serial) or ModbusTCP(NTP). ModbusRTU (serial) Enabling ModbusRTU Modbus RTU can be enabled with Protocol parameter ...
Timesynchronization with IEC61850 communication protocol
Enabling IEC61850 IEC61850 can be enabled at Communication > Protocols > IEC61850. Set the IP address used by IEC61850 at Communication > Connections. Time synchronization Set Time sync. source parameter to NTP at General menu. Set the NTP server IP ...
Timesynchronization with IEC103 communication protocol
Enabling IEC103 IEC103 can be enabled with Protocol parameter at Communication > Connections menu at Serial section. Set the Slave address at Communication > Protocols > IEC103. Time synchronization Set Time sync. ...