Setting up a simple circuit breaker status monitor and control

Setting up a simple circuit breaker status monitor and control

Enabling objects

For circuit breaker control AQ-200 series units use Objects. Objects can be enabled at Control > Functions enabled. Then the enabled object(s) can be found at Control > Objects.

Setting up indication and control signals.

In the INFO page choose which type of object is used: circuit breaker, withdrawable circuit breaker or a disconnector. Then in the same page set Object Status Open and Object Status Closed inputs and then set Object Close Command and Object Open Command. If withdrawable circuit breaker is used, signals for cart "in" and "out" statuses should be set too (Withdrw.CartIn.Status In and Withdrw.CartOut.Status.In).

Setting up event mask for event recording and SCADA communication

As the last step it is adviced to set up "event mask" at EVENT page of the object. In the EVENT page open.
    • Related Articles

    • Circuit breaker or disconnector status monitor and control with object function

      Circuit breakers and disconnector status and control in AQ-200 series units is done by Object function. Here is a typical setup of breaker/disconnector control and status indication. For more detailed description of objects refer to IED manuals. ...
    • Simulating breaker status with logic in AQ-200 series units

      If binary input statuses are not available for circuit breaker open/closed state it is still possible to simulate the status of the breaker for demonstration or test purposes. The following instructions show how to make a configuration for an object ...
    • Trip circuit open coil supervision with one digital input and connected trip output

      Trip circuit supervision is used to monitor the wiring from auxiliary power supply trough IEDs binary output and all the way to the open coil of the breaker. It is recommended to know that trip circuit is on healthy state when the breaker is closed. ...
    • Basics of auto-recloser function settings

      Auto-reclosing means a coordinated de-energization and re-energization of overhead lines (both transmission and distribution). Its purpose is to clear transient and semi-permanent fault causes from the line and automatically restore the supply to the ...
    • AQ-300 Trip Circuit Supervision

      Introduction All four fast acting trip contacts contain build-in trip circuit supervision function. The output voltage of the circuit is 5V(+-1V). The pickup resistance is 2.5kohm(+-1kohm). Our TRIP+ modules are improved to switch DC circuits. Using ...